Passive Cooling Technology

Category: Thermal Analysis – HVAC | Revised 2026-10-01
CAE visualization for passive cooling theory - technical simulation diagram
Passive Cooling Technologies

Theory: using the sky and the night as heat sinks

Overview

🙋

How realistic is cooling a building without air conditioning?

🎓

There are two natural heat sinks. One is the night sky: space is very cold, so on clear nights upward-facing surfaces radiate infrared and cool below air temperature. The other is cool night air, which pre-cools a building's concrete so it absorbs the next day's heat. Both use almost no energy, but their capacity is limited and depends on humidity and weather. So first cut cooling loads with insulation and shading, then estimate numerically how much of the remainder they can handle.

Radiative cooling

$$ P_{net} = \varepsilon\,\sigma T^4\,(1 - \varepsilon_{sky}) - (1 - R)\,G_{sun},\qquad \varepsilon_{sky} = 0.711 + 0.56\,\frac{T_d}{100} + 0.73\left(\frac{T_d}{100}\right)^2 $$

ε is surface emissivity, ε_sky clear-sky effective emissivity (Berdahl–Martin), T_d dew point (°C), R solar reflectance and G_sun solar irradiance. Convective gain from surrounding air is excluded.

Night ventilation and thermal storage

$$ \delta = \sqrt{\frac{\alpha P}{\pi}},\qquad E = \rho c\,\delta\,A\,\Delta T,\qquad \dot V = \frac{E}{\rho_a c_{p,a}\,\Delta T_{air}\,t_{night}} $$

δ is the depth reached by daily (P = 86,400 s) temperature swings. Concrete: conductivity 1.4 W/mK, density 2,300 kg/m³, specific heat 880 J/kgK. V̇ is the airflow needed to remove the heat over t_night with an air temperature rise ΔT_air.

Coffee Break Trivia

Daytime radiative cooling

Radiative cooling to the night sky has long been known; in arid regions it was used to freeze water overnight. Daytime cooling was thought impractical because solar heating dominates, but in 2014 Raman and colleagues at Stanford made a multilayer film that reflected 97% of sunlight while emitting strongly in the atmosphere's transparent infrared band (8–13 μm), cooling about 5 °C below ambient in direct sun. Daytime radiative-cooling materials have been an active field since.

Worked examples

Example 1: net radiative cooling (air 25 °C, emissivity 0.95)

Dew pointSky emissivityNightDay (95% reflectance)Day (85% reflectance)
10 ℃0.77496 W/m²56 W/m²−24 W/m²
15 ℃0.81180 W/m²40 W/m²−40 W/m²
20 ℃0.85263 W/m²23 W/m²−57 W/m²

Daytime sun is 800 W/m². Negative values mean net heating. A 25 °C blackbody emits 448 W/m², so net cooling is only 10–20% of that.

Example 2: night ventilation (100 m² exposed concrete)

ItemValue
Daily penetration depth0.138 m
Storage per m² per K279 kJ
Stored cooling at 3 K23.3 kWh
Daytime gains (30 W/m² × 10 h)30 kWh
Fraction absorbed78%
Night airflow needed (8 h, 4 K air rise)about 2,170 m³/h (7.2 ACH for 300 m³)
🙋

Even for white paint, 95% versus 85% reflectance flips cooling into heating.

🎓

Sunlight is 800 W/m², so a 10% difference in absorptance is 80 W/m² — about the size of night-time radiative cooling. Ordinary white paint looks white but absorbs some ultraviolet and near-infrared, often reflecting only 80–85%. Cooling below ambient by day needs a material that reflects sunlight almost completely while emitting strongly at 8–13 μm. Absorbing even a little sun backfires, so roof materials should be chosen on both solar reflectance and infrared emissivity. In humid regions, higher sky emissivity also shrinks the effect.

Planning and evaluation

  1. First reduce cooling loads with insulation and shading.
  2. Estimate radiative and night-ventilation effects from local temperature, dew point and cloud cover.
  3. For night ventilation, expose concrete indoors and secure ample airflow.
  4. Run hourly simulations of room temperature and check comfort.
  5. Plan backup cooling for humid periods when effects drop.
Coffee Break Trivia

“An office where night cooling failed”

An office added night ventilation, but next-day temperatures barely fell. The ceiling slab was concrete, but a suspended ceiling hung below it and carpet covered the floor. The concrete to be cooled was nearly isolated from room air, so it couldn't be cooled at night or absorb heat by day. Replacing the suspended ceiling with a highly perforated one cut next-day peak temperature by about 2 °C. Thermal mass must not only exist but be exposed to the air.

Common mistakes

Mistakes and fixes

MistakeEffectFix
Ignoring humidityRadiative cooling overestimatedSky emissivity from dew point
Judging reflectance by eyeHeats up by dayMeasure solar reflectance
Covering the concreteStorage ineffectiveExpose it to the room
Too little night airflowInsufficient pre-coolingCalculate required flow
Ignoring convective gainCooling overestimatedAccount for wind or covers
🙋

I'd like to learn related topics.

Related Simulators

Experience the theory firsthand with the interactive simulator for this field

All Simulators

Related fields

Structural AnalysisFluid Analysis (CFD)Manufacturing & Process Simulation
Rate this article
Thank you for your feedback!
Helpful
More details
Report error
Helpful
0
More details
0
Report error
0