System & Source Parameters
System Voltage V_sys6.6 kV
Source Short-Circuit Capacity S_sc500 MVA
Transformer
Transformer Capacity MVA_T10 MVA
Transformer %Z6.0 %
Transformer X/R Ratio10.0
Cable
Cable Length L100 m
R'/km (mΩ/m)0.206
X'/km (mΩ/m)0.080
Breaker Rated Interrupting Current25 kA
—
3-Phase Fault I [kA rms]
—
Peak Current [kA]
—
SLG Fault I_SLG [kA]
—
LL Fault I_LL [kA]
—
X/R Ratio (total)
—
Peak Factor κ
—
Z_total [mΩ]
—
Breaker Capacity Ratio
Short-Circuit Current Formulas
Three-phase fault current via Thevenin equivalent:
$$I_{3\phi} = \frac{V_{prefault}}{\sqrt{3} \cdot Z_{total}}$$Peak current: $I_{peak} = \kappa \cdot \sqrt{2} \cdot I_{3\phi}$, $\kappa = 1.02 + 0.98 e^{-3/(X/R)}$
SLG fault: $I_{SLG} = \dfrac{3V}{Z_1 + Z_2 + Z_0}$
LL fault: $I_{LL} = \dfrac{\sqrt{3} \cdot V}{Z_1 + Z_2}$
CAE Integration: Directly applicable to protective relay setting calculations, breaker capacity selection, and busbar thermal withstand calculation (I²t) per IEC 60909 and IEEE C37.13. Sensitivity analysis of transformer %Z can be instantly checked with the slider.