Short-Circuit Current Calculator Back EN · ZH
Protection Engineering

Short-Circuit Current Calculator (Symmetrical & Asymmetrical Faults)

Calculate three-phase, SLG, LL, and DLG fault currents using the symmetrical component method. Real-time analysis with transformer %Z, cable length, and breaker capacity comparison.

System & Source Parameters
System Voltage V_sys6.6 kV
Source Short-Circuit Capacity S_sc500 MVA
Transformer
Transformer Capacity MVA_T10 MVA
Transformer %Z6.0 %
Transformer X/R Ratio10.0
Cable
Cable Length L100 m
R'/km (mΩ/m)0.206
X'/km (mΩ/m)0.080
Breaker Rated Interrupting Current25 kA
3-Phase Fault I [kA rms]
Peak Current [kA]
SLG Fault I_SLG [kA]
LL Fault I_LL [kA]
X/R Ratio (total)
Peak Factor κ
Z_total [mΩ]
Breaker Capacity Ratio

Short-Circuit Current Formulas

Three-phase fault current via Thevenin equivalent:

$$I_{3\phi} = \frac{V_{prefault}}{\sqrt{3} \cdot Z_{total}}$$

Peak current: $I_{peak} = \kappa \cdot \sqrt{2} \cdot I_{3\phi}$,  $\kappa = 1.02 + 0.98 e^{-3/(X/R)}$

SLG fault: $I_{SLG} = \dfrac{3V}{Z_1 + Z_2 + Z_0}$

LL fault: $I_{LL} = \dfrac{\sqrt{3} \cdot V}{Z_1 + Z_2}$

CAE Integration: Directly applicable to protective relay setting calculations, breaker capacity selection, and busbar thermal withstand calculation (I²t) per IEC 60909 and IEEE C37.13. Sensitivity analysis of transformer %Z can be instantly checked with the slider.