Duct Acoustic Analysis
Theory: sound travelling in ducts
Overview
I want to reduce fan noise coming out of an HVAC duct. Where should the analysis start?
First check how sound propagates in the duct at the frequencies of interest. At low frequency it travels as a plane wave uniform across the section, easily analysed with 1D transfer matrices. At higher frequency, higher-order modes with cross-sectional pressure variation start to propagate and 3D analysis is needed; the boundary is the cut-on frequency. Then choose between absorptive lining that trims a broad band and resonators that cut specific frequencies hard.
Cut-on frequency and lined ducts
$c$ is the speed of sound, $a$ the longer rectangular side, $D$ the diameter. In Sabine's lined-duct formula, $\alpha$ is absorption coefficient, $P$ lined perimeter and $S$ cross-sectional area; narrower ducts have larger $P/S$ and attenuate more.
Side branch (quarter-wave tube)
At the frequency where the closed branch is a quarter wavelength long, pressure at the branch entrance vanishes and sound doesn't pass downstream. $S_b$ is the branch area and $\delta_{end}$ the entrance end correction (air moving slightly beyond the opening).
Organ pipes and silencers
Resonance in pipes has long been known through organ pipes and wind instruments. At a pipe's end the air vibrates slightly beyond the mouth, so the pipe sounds as if a little longer than it is. Lord Rayleigh derived this 'end correction' theoretically in the 19th century. In the 20th century, as noise reduction became important in car mufflers and HVAC ducts, the same principle was used in reverse: silencers that cancel specific tones with pipe resonance.
Worked examples
Example 1: plane-wave range
| Duct | Cut-on frequency |
|---|---|
| 600 × 300 mm | 286 Hz |
| 400 × 200 mm | 429 Hz |
| 1,000 × 500 mm | 172 Hz |
| 150 mm round | 1,340 Hz |
| 300 mm round | 670 Hz |
| 600 mm round | 335 Hz |
Example 2: lined duct attenuation (600×300 mm, four sides)
| Absorption coefficient | 0.3 | 0.5 | 0.7 | 0.9 |
|---|---|---|---|---|
| Attenuation | 1.9 dB/m | 4.0 dB/m | 6.4 dB/m | 9.1 dB/m |
Example 3: side branch tuned to 125 Hz
A closed 150 mm branch on a 300 mm round duct, with length set to c/(4f) = 0.686 m ignoring end correction. Transmission loss:
| Frequency | 100 Hz | 115 Hz | 120 Hz | 125 Hz | 130 Hz | 135 Hz | 150 Hz | 250 Hz |
|---|---|---|---|---|---|---|---|---|
| TL | 0.6 dB | 3.0 dB | 6.9 dB | Infinite (ideal) | 6.9 dB | 3.0 dB | 0.6 dB | 0.0 dB |
Infinite at 125 Hz, yet barely effective just off it.
Over 10 dB only from 121.7 to 128.3 Hz — 6.6 Hz. In reality losses such as air viscosity limit the peak to around 20–30 dB. And the biggest danger is end correction: at the branch entrance, air moves slightly beyond the opening, so the branch resonates as if about 45 mm longer. Forget it and resonance shifts to 117 Hz, leaving just 3.9 dB at 125 Hz; the correct length is 0.641 m. If fan speed varies and the tone moves, combining with absorptive treatment is safer than relying on a narrow resonance.
Analysis workflow
- Characterise source frequencies and levels (such as fan blade-passing frequency).
- Compare with cut-on to decide between 1D transfer matrices and 3D analysis.
- Assemble overall transmission including bends, branches, area changes and outlet radiation.
- Add absorptive or resonant treatment and verify including end corrections and flow effects.
- With flow, check self-generated flow noise of the silencer itself.
“Only the low hum won't go”
A meeting room received complaints of a low hum from the HVAC outlet. The ducts had ample absorptive lining, but the tone was about 80 Hz, where lining barely works — and the duct outlet strongly reflects low frequencies, setting up standing waves inside. Adding a side branch tuned to the fan's blade-passing frequency, with its length corrected for end effects, cut the hum substantially. Resonators for low frequencies, absorption for high: that's the basic split.
Common mistakes
Mistakes and fixes
| Mistake | Effect | Fix |
|---|---|---|
| Forgetting end correction | Resonance misses the target | Size length with correction |
| 1D analysis above cut-on | Higher modes missed | 3D analysis |
| Using lining for low tones | Little effect | Add resonators |
| Ignoring outlet reflection | Standing waves missed | Outlet radiation impedance |
| Ignoring flow effects | Silencer generates noise | Evaluate flow noise |
I'd like to try related calculations.
Try the duct silencer attenuation calculator, muffler transmission loss tool, Helmholtz resonator calculator and acoustic standing wave simulator. Related analyses include muffler design, vibro-acoustics and aeroacoustics.
Related Topics
Experience the theory firsthand with the interactive simulator for this field